Sentry-6002 NEMA 4 protection grade battery monitoring system for 120V and 240VDC
Sentry-6002NEMA is a powerful battery monitoring system for substations with vented (flooded) or valve regulated lead acid batteries. It has been re-designed based upon our field proven BM6500 (1996) and BM6800 (2007) models to provide effective remote battery management according to the IEEE updated standards:
IEEE Std. 1188 – 2005: Recommended Practice for Maintenance, Testing, and Replacement of Valve-Regulated Lead- Acid (VRLA) Batteries for Stationary Applications (IEEE Link)
IEEE Std. 450 – 2010: Recommended Practice for Maintenance, Testing, and Replacement of Vented Lead-Acid Batteries for Stationary Applications (IEEE Link)
Main Features
- Ultra precise IR (Internal Resistance) measurement for each cell detects dry-out and deterioration/capacity loss long before a problem occurs.
- Discriminate inter-cell and battery to bus connection resistance to identify connection problem without a discharge.
- Ambient and multi-point pilot battery temperature monitoring.
- IP65 (NEMA4) grade protection allows unit(s) to be installed inside the battery room. Compact design allows for easy installation on a rack or wall.
- Automatic discharge capture to database to record planned load test and unplanned power outage.
- No mechanical scanning relays, resulting high reliability.
- Plug & play HMI (optional) allows field service without a computer.
- Industry standard Modbus-RTU and Modbus-TCP communication.
- Full support to SNMP networking battery management system
- Compatible with Battery Analyzer software and MyBattery Platform™ for cloud based remote monitoring.
Specifications
Power Supply | |
Power Input | Internal DC/DC converter, 90 – 150V input; Maximum Consumption: 10W 250VDC version available |
Current/Temperature Measurement | |
Current Transducer (CT) | Support LEM current transducer with internal +/-12V power supply Default CT: HTA 300-S, measurement range +/- 450A, window size D-32mm.Accuracy: 0.1% + sensor accuracy |
Temperature Sensing | 1 ambient temperature sensor, 2 pilot temperature sensors Measurement range: -20⁰C to 60⁰C, operating range: 5⁰C to 40⁰C (41⁰F to 104⁰F)Accuracy: 1 ⁰C |
Voltage Measurement | |
Battery | 60 x 2V cell per unit, up to 3,000Ah For 120 x 2V application, 2 units are required for each string. For large UPS 240 x 2V application, 4 units are required for each string. |
Bus Voltage | Range: 90 – 160V per unit; Accuracy: 0.1% |
Input Range to Each Channel | +/- 3V for 2V batteries |
Accuracy | 0.1% |
Input Wiring | 2-wire sampling for each battery, UL 300V 12-conductor 20AWG cable recommended |
Internal Resistance and Connection Resistance | |
Range and Resolution | 0 to 3mΩ, 0.005 mΩ resolution |
2-wire mode | Internal Resistance and discriminate Connection Resistance. |
Communication | |
Serial Port | Isolated RS-232C and RS-485 interface MODBUS RTU, 9600-8-1-NoneModbus address 1 to 28, configurable with HMI |
Ethernet | Onboard DTU to MyBattery Platform or Battery Analyzer software Modbus-TCP for integration |
Indication and Alarm | |
LED indication |
|
Alarm Outputs | Service Alarm (Normal Close, 0.1A capacity)Urgent Alarm (Normal Close, 0.1A capacity) |
Dimensions | |
Unit Dimensions | 13.50” (H) x 11.27” (W) x 7.18” (D) 343mm (H) x 286mm (W) x 182mm (D) |
Weight | 10 lbs per unit (about 4.5kg) |
*Specifications subject to change without notice
Sentry-6002NEMA Datasheet (pdf)
Sentry-6002NEMA Connection Schematics (pdf)