Sentry-1202 Telecom Battery Monitoring System
For 24V systems with high capacity 2V cells
Sentry-1202 is a powerful battery health monitoring system for Telecom 24V system with 2V cells up to 3,000Ah capacity. This compact battery unit combines superior data quality and flexible installation to address most cell site applications for effective remote battery management according to the IEEE updated standards:
IEEE Std. 1188 – 2005: Recommended Practice for Maintenance, Testing, and Replacement of Valve-Regulated Lead- Acid (VRLA) Batteries for Stationary Applications (IEEE Link)
IEEE Std. 1491-2012: IEEE Guide for Selection and Use of Battery Monitoring Equipment in Stationary Applications (IEEE Link)
[ngg src=”galleries” ids=”7″ display=”pro_mosaic”]
-
Onboard Battery State of Health (SOC) analysis.
-
Reliable Remaining Runtime prediction.
-
Compatible with MyBattery Platform™ for large scale deployment
-
Easy integration to existing site management software
- Individual high resolution Internal Resistance / Conductance online measurement for 2V cells
- Individual inter-cell connection resistance to further improve IR accuracy
- Proprietary technology to monitor float current without external sensor
- Ethernet and Wireless M2M compatible, instant drop-in with no field configuration
- Battery Analyzer and MyBattery Platform™ compatible
- Modbus-RTU or Modbus-TCP for integration for 3rd party software
- Effectively priced for large scale applications
Specifications
Power Supply | |
Power Input | Powered by battery bus, 18-30V Maximum Consumption: 10W Average Consumption: 3W |
Isolation | [email protected] to battery string |
Current/Temperature Measurement | |
Current Sensor
(Optional) |
Support LEM HAS current sensor with internal +/-12V power supply
(Default range +/- 400A, window size 20mmx15mm) |
Accuracy | 0.1% + sensor accuracy |
Temperature Sensors | 1 ambient temperature sensor 1 pilot temperature sensor |
Range | Measurement range: -40 to 65⁰C |
Accuracy | 1 ⁰C |
Voltage Measurement | |
Battery | 12 x2V cell, up to 3,000Ah |
Bus Voltage | Range: 18 – 30V; Accuracy: 0.1% |
Battery Voltage | +/- 3V for 2V batteries |
Accuracy | 0.1% |
Input Wiring | 2-wire differential input for each battery |
Internal Resistance | |
Range and Resolution | 0 to 3mΩ, 0.001 mΩ resolution |
2-wire mode | Internal Resistance and discriminate Connection Resistance. |
Communication | |
Serial Port | Isolated RS-232C and RS-485 ports |
Modbus | MODBUS RTU, 9600-8-1-None |
Ethernet | 10/100Mbps BaseT with RJ-45
Onboard Ethernet DTU to MyBattery Platform Embedded web page for real-time data |
Wireless Option | GSM/GPRS (PTCRB, AT&T, T-Mobile, Jasper, and Rogers Network Certified) |
Indication and Alarm | |
LED indication | Dual-color LEDs for status
Orange LED for service alarm Red LED for urgent alarm |
Alarm Outputs | Service Alarm (Normal Close, 0.1A)
Urgent Alarm (Normal Close, 0.1A) |
Mechanicals | |
Dimensions | 165W * 31H *165L (mm) (Mounting bracket excluded) |
Mounting | DIN Rail, magnetic cup or customized bracket |
*Specifications subject to change without notice