Ask a question

Remote Battery Monitoring for Substations

BatteryDAQ delivers all elements of a state-of-art battery monitoring solution.  Flexibility and industry-specific designs are two keys to our success.

Substation 1 200

 

Sentry-6002 with wiring 200

 

wet 60x2V 200

Sentry-6002 installation 200

 

sites overview 200

 

24x2V low capacity 200

 

Key features to enable NERC PRC-005 complaince and streamline battery maintenance

  1. NEMA 4 (IP65) grade protection, so system can be installed in battery room or control room for long term reliable operation
  2. String voltage, cell voltage, float current 24/7 monitoring
  3. High resolution ohmic measurement (internal resistance/impedance) for each cell
  4. Inter-cell connection resistance
  5. Ambient and pilot temperature
  6. Optional electrolyte monitoring
  7. Optional unintentional battery ground detection
  8. Plug and play tool to check battery data and set paramaters
  9. Ethernet with static IP or DHCP
  10. 3G/4G wireless option
  11. Access data anywhere with internet (can be restricted within utility private network.)
  12. MyBattery platform to handle unlimited sites with secured access
  13. Easy integration to existing central management system with data/graph/map.
  14. High level reporting for realtime outage and statistics
  15. Data management compatible with handheld Sentry Battery Inspector.

 

DC Power

Battery Configuration

BatteryDAQ Model/Link

Remark

-48V

24x2V, vented/flooded or valve regulated (VRLAB)

Sentry-30EX

Install in battery room or control room

-48V

24x2V, VRLAB

Sentry-2402W2

Install in control room

125V

60x2V, vented/flooded or valve regulated (VRLAB)

Sentry-6002NEMA

Install in battery room or control room

125V

Ni-Cad, 97x1.2V vented

Sentry-6002NEMA

or

Sentry-2412 (low cost)

Install in battery room or control room

User’s preference to monitor at cell level or multiple cells

125V

10x12V, VRLAB

Sentry-2412

Install control room or cabinet

250V

120x2V, vented/flooded or valve regulated (VRLAB)

Sentry-6002NEMA

Install in battery room  or control room

2 units (2x60=120) for one string

250V

Ni-Cad, 194x1.2V vented

Sentry-6002NEMA

or

Sentry-2412 (low cost)

Install in battery room or control room

User’s preference to monitor at cell level or multiple cells

250V

18x12V, VRLAB

Sentry-2412

Install in control room or cabinet

made in usa   RoHs CE UL-1   UL-2